ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 87
Reaction on preset 1 (telegr. value 0)
Options:
no reaction
ON
OFF
restore old value before preset 2
restore parameterized value of preset 2
This parameter determines the contact position that the output assumes when preset 1 is recalled, i.e.,
communication object
Call Preset 1/2
receives a telegram with the value 0.
The following functions can be selected as further selection options:
•
no reaction
: No switching action is undertaken with a preset recall. The preset is ignored. The preset
is also ignored on storage via the bus, i.e., no value is saved, the preset remains inactive.
•
restore old value before preset 2:
The current relay contact position is stored when preset 2 is first
recalled. This stored value (switch state) is retained until it is set again by the recall of preset 1.
The current contact position is stored again next time preset 2 is recalled.
Example
With preset 2, the lighting in a conference room is recalled for a presentation. When the presentation is
finished, the lighting is restored via preset 1 to the state it was in previously.
•
restore parameterized value of preset 2
: resets preset 2 to the parameterized value. This can be
advisable if preset 2 can be stored via the bus, see below.
Please note
With options
restore old value before preset 2
or
restore parameterized value of preset 2
, saving the
preset concerned has no effect. The saved value is not recalled, but rather the parameterized function is
undertaken.