The following parameters appear when Staircase lighting is selected:
Duration of staircase lighting
Minutes
Options:
0…5…1,000
Seconds
Options:
0…59
The staircase lighting time defines how long the staircase lighting is switched on after an ON
telegram. The input is made in minutes and seconds. The staircase lighting time may extend
depending on the value set in the parameter
Warning before end of staircase lighting
.
Extending staircase lighting by
multiple operation ("pumping up")
Options:
no (not retriggerable)
yes (retriggerable)
up to max. 2 x staircase lighting time
up to max. 3 x staircase lighting time
up to max. 4 x staircase lighting time
up to max. 5 x staircase lighting time
If a further ON telegram is received during the staircase lighting time sequence, the remaining
staircase lighting time can be extended by a further period. This is possible by repeated operation
of the button (“pumping up“) until the maximum parameterized number of retriggering operations is
reached. The maximum time can be set to 1, 2, 3, 4 or 5 times the staircase lighting time.
Let's say the staircase lighting time has been extended by “pumping up” to the maximum time.
If some of the time has already timed out, the staircase lighting time can be re-extended to the
maximum time by “pumping up”.
However the parameterized maximum time may not be exceeded.
•
no (not retriggerable)
: The receipt of an ON telegram is ignored. The staircase lighting time
continues without modification to completion.
•
yes (retriggerable)
: New ON telegrams reset the staircase lighting time and starts to count
again. This process can be repeated as often as desired using this selection.
•
up to max. 2/3/4/5 x staircase lighting time
: New ON telegrams extend the staircase lighting
time by 2/3/4/5 times the staircase lighting time.