ABB i-bus
KNX
Commissioning
102 2CDC 505 056 D0208 | SA/S
Datapoint type object "Current Value"
[0...65,535 in mA]
Options:
2 byte counter (DTP 7.012)
4 byte float (DTP 14.019)
This parameter determines the data type (datapoint, DTP) of the communication object
Current Value
.
A 2 byte counter (EIS 10, DPT
7.012, 1 mA per digit) or a 4 byte float value (EIS 9, DTP 14.019) can be
selected.
Please note
The current detection range is designed for currents between
20 mA and 20 A.
Send current value, transmission time
[0…65,535s; 0 = not send]
Options:
0
1…65,535
This parameter determines if and at which intervals the present current value is sent via communication
object
Current Value
. The cycle time must be entered in seconds.
•
0
: No current values are sent cyclically via the bus. The present current values are however
continuously available in the output's
Current Value
communication object, and can be read out.
Send current value on change of value
Options:
no
25/50/100/200/500 mA
1/2/5 A
This parameter determines that on a load change the current value is sent via the bus via the
Current
Value
communication object. A current value is always sent via the bus if the current change is greater
than the current value set in this parameter. The current value sent via the bus applies as a new reference
value.
•
no
: No current value is sent.
The smaller the current value set, the more precisely the sent value will correspond with the actual value.
Highly fluctuating current values may result in a high bus load.
For further information see:
Current detection specifications
, p. 44