ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 129
3.2.5.1.2
Parameter window A: Forced Operation
All settings for the
Forced Operation
function are undertaken in this parameter window.
This parameter window is visible if the
Enable function "forced operation"
parameter
has been enabled in
Parameter window
A: Function
,
p
.
124.
During a forced operation, the Switch Actuator triggers a freely adjustable forced position. This has the
highest priority, i.e. it is not modified by a valve purge or safety position.
Forced operation can be
activated via communication object
Forced operation = "1"
and
deactivated via
Forced operation = "0"
.
Valve position during forced positioning
Options:
unchanged
0% (closed)
10% (26)
...
90% (230)
100% (open)
The valve position triggered by the actuator during the forced operation is determined by this parameter.
The value in brackets corresponds to the 1 byte value.
The switch cycle time t
CYC
used for control should be set in the parameter
cycle time
for continuous control
in parameter window
A: General.
When forced operation ends the Switch Actuator returns to its normal method of operation and calculates
its next contact position value from the incoming values on communication objects
Switch
or
Control value
(PWM)
.