3.2.3.1.2
Parameter window A: Preset
Preset settings can be made in this parameter window.
This parameter window is visible if
Enable function "presets" has
been enabled in
Parameter window
A: Function
, p.
71.
What is a preset?
Presets are used to recall a parameterized switch value, e.g. in order to implement light scenes.
In addition, the output value that is currently set can be saved as a new preset value.
The preset values can be set (stored) via the bus. In parameter window A:
General
you define
whether the values set in ETS are transferred to the Switch Actuator with a download. This is how
the values saved in the actuator are overwritten.
Two presets are available per output. Preset 1 is recalled by a telegram with the value 1, Preset 2 is
recalled by a telegram with the value 0. Separate communication objects are available for recalling
and for saving/setting a preset.
Preset telegrams continue to be executed when the Staircase lighting function is set. The Staircase
lighting function is triggered by a preset recall (ON telegram).