Lamp output load 16 A
Lamps
Incandescent lamp load
2,500 W
Fluorescent lamps T5/T8
Uncorrected
Parallel compensated
DUO circuit
2,500 W
1,500 W
1,500 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
Halogen lam
ps 230 V
1,200 W
1,500 W
2,500 W
Dulux lamp
Uncorrected
Parallel compensated
1,100 W
1,100 W
Mercury-vapor lamp
Uncorrected
Parallel compensated
2,000 W
2,000 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150
µ
s)
Maximum peak inrush current I
p
(250
µ
s)
Maximum peak inrush current I
p
(600
µ
s)
400 A
320 A
200 A
Number of electronic ballasts (T5/T8, single
element)
1)
18 W (ABB EVG 1 x 18 SF)
24 W (ABB EVG-T5 1 x 24 CY)
36 W (ABB EVG 1 x 36 CF)
58 W (ABB EVG 1 x 58 CF)
80 W (Helvar EL 1 x 80 SC)
23
23
14
11
10
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush
current of the electronic ballasts, see
Ballast calculation
, p. 42
Device type
Application program
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
SA/S 2.10.2.1
Switch 2f 10A/…*
34
254
254
SA/S 4.10.2.1
Switch 4f 10A/…*
64
254
254
SA/S 8.10.2.1
Switch 8f 10A/…*
124
254
254
SA/S 12.10.2.1
Switch 12f 10A/…*
184
254
254
* … = current version number of the application program
Please note
ETS and the current version of the device application program are required for programming.
The current application program is available for download at
www.abb.com/knx
. After import into ETS,
it is available in ETS under
ABB/Output/Binary output
xf 10A/…* (x = 2, 4, 8 or 12).
The device does not support the locking function of a KNX device in ETS. If you inhibit access to all
devices of the project with a
BCU code
, it has no effect on this device.