ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 65
Control period in seconds
[0…65,535s, 0 = inactive]
Options:
0…65,535
This parameter defines the monitoring period of the
Safety Priority x
function. If during this time
communication object
Safety Priority x*
receives a telegram with the triggering condition defined in
parameter
Function Safety Priority x
, it will be triggered. Should the communication object
Safety Priority x*
receive a telegram that does not fulfill the trigger conditions, the control period is reset and restarted.
•
0
: No monitoring is taking place. However, the
Safety Priority x
is triggered if communication object
Safety Priority x receives
a telegram with the triggering condition as defined in parameter
Function
Safety Priority x
*x = 1, 2 or 3
Please note
The monitoring period in the Switch Actuator should be at least twice as long as the cyclical
transmission time of the sensor, so that the absence of an individual signal, e.g. due to a high bus load,
does not immediately trigger an alarm.