ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 93
Gate disabled, if Object value "Logical
Connection 1" is
Options:
1
0
This parameter defines the value at which communication object
Logical Connection 1
disables the
GATE.
While it is disabled, telegrams received on communication object
Switch
are ignored. As long as
GATE is active, the last value sent to the GATE input remains on the output's logic gate.
When disabled, the value that was on the output beforehand remains.
After the GATE is enabled, this value will be retained until a new value is received.
For further information see:
Function diagram
, p. 147
The GATE is deactivated on bus voltage failure and remains so on bus voltage recovery.
Logical Connection 2
The same programming options exist as those for parameter
Logical Connection 1
.