ABB i-bus
KNX
Commissioning
116 2CDC 505 056 D0208 | SA/S
No.
Function
Object name
Data type
Flags
20
Forced Positioning
Output A
2 bit (EIS 8)
DPT 2.001
C, W
This communication object is enabled if in parameter window
A: Function
the
yes
option has been selected for parameter
Enable functions "priority and safety operation"
and
2 bit object
is selected for parameter
Contact position if forced operation
.
The output can be forcibly operated via this communication object (e.g. by a higher-level control). The communication object
value directly defines the forced position of the contact:
0 or 1 = The output is not forcibly operated.
2 = The output is forcibly switched off.
3 = The output is forcibly switched on.
At the end of the forced operation, a check is performed to see if one of the three
Safety Priority x
functions (x = 1, 2 and 3) is
active. If necessary, the contact position is set by the active safety priorities. If no
Safety Priority x
is active, the parameter
used is the one set in parameter window A:
Safety
, for parameter
Reaction when forced operation and all Safety Priority x end
.
Please note that the function
Safety Priority 1
and a bus failure have a higher priority on the contact position:
see
Function diagram
, p. 147.
21
Threshold input
Output A
1 byte (EIS 6)
2 byte (EIS 10)
DPT 5.010
DPT 7.001
C, W
This communication object is enabled if the
yes
option is selected for parameter
Enable function "threshold"
in the
A: Function
parameter window.
Depending on the selection made in parameter window A:
Threshold
, a 1 byte (integer value) or 2 byte (counter value)
communication object is enabled.
If the threshold value parameterized in window A:
Threshold
is overshot, a switching action can be performed.
22
Change Threshold value 1
Output A
1 byte (EIS 6)
2 byte (EIS 10)
DPT 5.010
DPT 7.001
C, W
This communication object is enabled if the
yes
option has been selected for parameter
Change Threshold 1 over bus
in
parameter window A:
Threshold
.
Depending on the selection made in parameter window A:
Threshold
, a 1 byte (integer value) or 2 byte (counter value)
communication object is enabled.
If the communication object
Change Threshold value 1
is enabled, the threshold value can be changed via the bus.
23…
24
Not assigned