ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 107
Value of hysteresis current
threshold 1
Options:
3/25/50
/100/200/500 mA
1/2/5 A
To avoid a continuously changing threshold value state, the current detection thresholds feature a
hysteresis function. The set
Value of hysteresis current threshold
ensures that a current change is
only registered as such if it is greater than the hysteresis value. Only then will a change of current
threshold value status be sent.
Partly due to fluctuations in the electrical system and the detection accuracy of the current
transformers in the Switch Actuator, 3 mA is the smallest hysteresis possible.
For further information see:
Threshold
function with current detection
, p. 142 and
Current detection
specifications
, p. 44
Please note
No hysteresis is used with the option none. With a highly fluctuating current value this can often
lead to frequently changing threshold results. The bus load increases unnecessarily if there is
continuous status change.
Current threshold 1
+/- hysteresis
Options:
no sending
send "0" at crossing over
send "1" at crossing over
send "1" at crossing lower
send "0" at crossing lower
send "0" at crossing over – "1" at crossing lower
send "1" at crossing over – "0" at crossing lower
This parameter determines the value of the communication object
Status Current-Threshold 1
when
undershooting or overshooting current threshold value 1.
•
no sending:
no telegram is sent when there is a current threshold value overshoot or
undershoot
•
send "0" at crossing over:
Should current threshold value 1 be overshot, communication object
Status Current-Threshold 1
sends
the value 0. An undershoot sets the value to 1 but no
telegram is sent.
•
send "1" at crossing over
: Should current threshold value 1 be overshot, communication object
Status Current-Threshold 1
sends
the value 1. An undershoot sets the value to 0 but no
telegram is sent.
•
send "0" when crossing lower
: Should current threshold value 1 be undershot, communication
object
Status Current-Threshold 1
sends the value 0. An overshoot sets the value to 1 but no
telegram is sent.