ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 137
No.
Function
Object name
Data type
Flags
12
Status valve purge
Output A
EIS 1, 1 bit
DPT 1.002
C, T
This communication object is enabled if the
yes
option is selected for parameter
Enable function "valve purge"
in the
A:
Function
parameter window.
The status of the valve purge is visible via this communication object.
Telegram value:
0 = valve purge not active
1 = valve purge active
Please note
The status is displayed as soon as a purge has been activated. The status remains active even when the
purge has been interrupted, e.g. by a priority.
13
RTR fault
Output A
EIS 1, 1 bit
DPT 1.005
C, T
This communication object is enabled if the
yes
option is selected for parameter
Enable monitoring of the controller
in the
A:
Function
parameter window.
Using this communication object, communication objects
Switch
and
Control value (PWM)
can be cyclically monitored. If the
room thermostat (RTR) values are missing, the device assumes that the thermostat is malfunctioning and signals a fault.
Telegram value:
1 = fault
0 = no fault
14
Forced operation
Output A
1 bit (EIS 1)
DPT 1.003
C, W
This communication object is enabled if the
yes
option is selected for parameter
Enable function "forced operation"
in the
A:
Function
parameter window.
If the communication object receives the value 1, the valve is forcibly moved to the parameterized position set in parameter
window A:
Forced Operation
. The forced positioning of the valve continues until forced operation is ended, which happens
when a telegram with value 0 is received via communication object
Forced operation
.
Please note that the
Forced operation
function and a bus voltage failure have a higher priority on the contact position,
see
Function diagram
, p. 147.
15
Status heating
Output A
EIS 6, 1 byte
DPT 5.010
C, W
This communication object is visible if control of the heating actuator is implemented via a 1 bit communication object,
e.g. within a continuous control, and feedback of the control value is parameterized with a 1 byte value.
The current 1 byte control value of the output is sent via this communication object.