ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 103
If the parameter
Send current value, transmission time [0...65,535s, 0 = not send]
is also activated,
the counter is reset and restarted after sending the current value.
Please note
If for example, a current change of 1 A has been selected, a current value is only sent if the load current
exceeds 1 A when starting, for example, from 0 A. This means that no current value is sent (displayed)
when a current of 0.9 A is flowing.
The other way around, a current value can be displayed (sent) even though no current is flowing.
Starting from 1.5 A the current is reduced to 0 A. A current value of 0.5 A is sent via the bus. Since no
further 1 A current change can occur for a current value of 0, no new value is sent. The last value sent
and displayed is 0.5 A.
These inaccuracies can be prevented by additional activation of the parameter
Send current value,
transmission time [0...65,535s, 0 = not send]
or if a sufficiently small current change has been selected.