Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
6 Programming
50
COI/AZ30E–EN Rev. D
…Device Setup
Oxygen Setup
%O2 Range Hi
Sets the maximum oxygen concentration
[0.01 to 100 % O
2
*]
25.00 %O
2
%O2 Range Lo
Sets the minimum oxygen concentration
[0.01 to 100 % O
2
*]
0.01 %O
2
Filter Time
Sets the amount of filtering time required on the oxygen
input measurement.
Note
. This is a rolling-average filter.
[1 to 60 s]
1 s
Pressure Comp.
Sets the pressure compensation value.
Note
. Set a value if, in normal operation, positive or
negative pressure with respect to the pressure during a
calibration is present. If calibrations are performed at the
same pressure as normal operation, set this value to
0.00 psi.
[– 5.00 to 5.00 psi]
0.00 psi
Temp. Setup
Selects thermocouple type and temperature units.
Thermocouple Type
Selects the thermocouple type used for cell temperature
measurement.
For heated probes (AZ30) this is fixed as type K. For
unheated probes (AZ35), select the thermocouple type
used in the probe.
K
[–100 to 1300 °C (–148 to 2372 °F)]
K
B
[–18 to 1800 °C (–0.4 to 3272 °F)]
N
[–200 to 1300 °C (–328 to 2372 °F)]
R
[–18 to 1700 °C (–0.4 to 3092 °F)]
S
[–18 to 1700 °C (–0.4 to 3092 °F)]
Temperature Units
Selects the temperature units to be used in the
transmitter.
°C
*The Endura AZ30 oxygen systems must be used only for measuring non-oxygen enriched gasses (not more than 21 %
oxygen [air]) at pressure no greater than 1.1 bar absolute (44 in. WG). Operating the system in oxygen-enriched
atmospheres will invalidate / compromise certification.
Parameter
Comment / [Range]
Default
Table 6.9 Device Setup Menu (Continued)