Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
6 Programming
COI/AZ30E–EN Rev. D
65
6.4.8 Communication
Used to configure HART communication parameters and
cyclic output communication via the IrDA interface on the front
of the transmitter.
Parameter
Comment / [Range]
Default
HART
HART Poll Address
Used to enter a unique device address.
When set to 0,
Current Output 1
is active and provides
an analog output proportional to its source. HART
operates in point-to-point mode.
If set between 1 and 15,
Current Output 1
is fixed at 4
mA and HART operates in multi-drop mode.
Note
. See Section 8.2, page 74 for multi-drop
configuration details.
[0 to 15]
0
HART Device ID
The unique ID for the HART device.
Factory-set
read-only ID
HART Tag
Used to enter a user-defined tag for the HART device
(transmitter), selected from the alphanumeric character
set displayed when the
Edit
button is selected at this
sub-parameter.
[0 to 8 characters]
N / A
HART Device Message
Used to specify a a user-defined message for the HART
device (transmitter), selected from the character set
displayed when the
Edit
button is selected at this
sub-parameter.
[0 to 16 characters]
N / A
HART Descriptor
Used to specify a unique HART descriptor, selected from
the character set displayed when the
Edit
button is
selected at this sub-parameter.
Maximum of 32 characters.
N / A
Device Install Date
The time and date of installation.
User-set
Final Assembly No.
The device's (transmitter’s) final assembly (ID) number.
Factory-set
Table 6.13 Communication Menu
8
Menu
Exit
Select
Communication