Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
6 Programming
COI/AZ30E–EN Rev. D
63
…Input/Output
…Current Output 1
Elec. Range Hi
Selects the electrical range high current output value.
[3.80 to 22.00 mA]
mA
20.00 mA
Elec. Range Lo
Selects the electrical range low current output value.
[3.80 to 22.00 mA]
mA
4.00 mA
Output Failure
When
Enabled
, the current output can be driven to a
preset value if a
Failure
category diagnostic state
occurs – see page 84.
Disabled
Enabled
Disabled
Failure Current
Sets a preset value that the current output is driven
to when a
Failure
category diagnostic state is present
– see page 84.
Available only if
Output Failure
is
Enabled
.
[3.80 to 22.0 mA]
22.00 mA
Output #1 Test
Selects % output levels for
Current Output 1
.
When this parameter is exited, the current output
returns to its normal operating value.
[0, 25, 50, 75 or 100 %]
0
Parameter
Comment / [Range]
Default
Table 6.12 Input/Output Menu (Continued)