8 HART®-Protocol
COI/AZ30E–EN Rev. D
79
8.5 Device Status Information
8.5.1 Field Device Status First Byte
First Bit is set to 1
Description
Bit #7
Set to 1 = communications error
Bit #6
Vertical parity error
Bit #5
Overrun error
Bit #4
Framing error
Bit #3
Longitudinal parity error
Bit #2
Reserved
Bit #1
Buffer overflow
Bit #0
Reserved
First Bit is set to 0
Description
Bit #7
Set to 0
0x00 hex = 0 dec
No command-specific error
0x02 hex = 2 dec
Invalid selection
0x03 hex = 3 dec
Passed parameter too large
0x04 hex = 4 dec
Passed parameter too small
0x05 hex = 5 dec
Too few data bytes received (incorrect byte count)
0x06 hex = 6 dec
Device-specific command error
0x07 hex = 7 dec
In write protect mode
0x09 hex = 9 dec
Lower range value too high
0x0A hex = 10 dec
Lower range value too low
0x0B hex = 11 dec
Upper range value too high
0x0C hex = 12 dec
Upper range value too low
0x0D hex = 13 dec
Upper und lower range values out of limits
0x0E hex = 14 dec
Span too small
0x10 hex = 16 dec
Access restricted
0x12 hex = 18 dec
Invalid units code
0x20 hex = 32 dec
Busy
0x40 hex = 64 dec
Command not implemented
Table 8.4 Field Device Status First Byte