II K 4-14
Overview of Software
4.2.5 Macro 5 - Jogging
Description of I/O’s functionality
I/O
Param
Function
DI1
Direction of rotation. DI1=0=forward , DI1=1=reverse
DI2
Jog speed 1. Speed can be defined in parameter 5.13.
Accel/Decel Ramp for Jogging can be defined in parameter 5.19/5.20.
DI3
Jog speed 2. Speed can be defined in parameter 5.14.
Accel/Decel Ramp for Jogging can be defined in parameter 5.19/5.20.
DI4
2.01
not used
DI5
Emergency stop. Closed-circuit principle, must be closed for operation
DI6
Reset. Faultacknowledgement, reset faults signaled by the drive
DI7
Drive ON / OFF. DI7=0=OFF , DI7=1=ON
DI8
Drive START / STOP. DI8=0=STOP , DI8=1=START
DO1
6.11
Ready for Run. Converter switched ON, but not yet STARTed
DO2
6.12
Zero-speed signal. Motor at standstill
DO3
6.13
At set point. Speed reference = speed actual
DO4
6.14
Group fault signal. Common signal for all faults or alarms
DO5
6.15
Main contactor on. Controlled by ON command (DI7)
AI1
5.01
Speed reference
AI2
5.26
Additional speed reference
AO1
6.05
Speed actual
AO2
6.08
Torque actual
Mutual locking of Jog speed 1 – Jog speed 2 – Drive START
Jog 1
DI2
Jog 2
DI3
START
DI8
Drive is ON (DI7=1)
0
0
0
Drive is STOPped (Current controller disabled)
1
0
0
Drive STARTed via DI1 , speed reference=parameter 5.13
x
1
0
Drive STARTed via DI2 , speed reference=parameter 5.14
x
x
1
Drive STARTed via START command (DI8) , speed reference via analog input AI1
Parameter settings,
shaded areas are set by macro - all others are set during
commissioning
1 - Motor Settings
2 - Operation Mode
3 - Armature
5 - Speed Controller
6 - Input/Output
1.01 Arm Cur Nom
2.01 Macro Select
[Jogging]
3.04 Arm Cur Max
5.01 Speed Ref Sel
[AI1]
6.01 AI1 Scale 100%
1.02 Arm Volt Nom
2.02 Cmd Location
[Terminals]
3.07 Torque Lim Pos
5.02 Speed Meas
Mode
6.02 AI1 Scale 0%
1.03 Field Cur Nom
2.03 Stop Mode
3.08 Torque Lim Neg
5.03 Encoder Inc
6.03 AI2 Scale 100%
1.04 Field Volt Nom
2.04 Eme Stop Mode
3.14 Cur Contr Mode
[Speed Contr]
5.09 Accel Ramp
6.04 AI2 Scale 0%
1.05 Base Speed
3.15 Torque Ref Sel
[Const Zero]
5.10 Decel Ramp
6.05 AO1 Assign
[Speed Act]
1.06 Max Speed
3.17 Stall Torque
5.11 Eme Stop Ramp
6.06 AO1 Mode
3.18 Stall Time
5.12 Ramp Shape
6.07 AO1 Scale 100%
5.13 Fixed Speed 1
6.08 AO2 Assign
[Torque Act]
5.14 Fixed Speed 2
6.09 AO2 Mode
5.15 Zero Speed Lev
6.10 AO2 Scale 100%
5.16 Speed Level 1
6.11 DO1 Assign
[Rdy for Run]
5.17 Speed Level 2
6.12 DO2 Assign
[Zero Speed]
5.19 Jog Accel Ramp
6.13 DO3 Assign
[At Setpoint]
5.20 Jog Decel Ramp
6.14 DO4 Assign
[Flt or Alarm]
5.21 Alt Par Sel
[Sp < Lev1]
6.15 DO5 Assign
[Main Cont On]
5.26 Aux Sp Ref Sel
[AI2]
6.22 MSW Bit 11 Ass
[none]
6.23 MSW Bit 12 Ass
[none]
6.24 MSW Bit 13 Ass
[none]
6.25 MSW Bit 14 Ass
[none]