II K 4-8
Overview of Software
4.2.2 Macro 2 - Man/Const Sp
Description of I/O’s functionality
I/O
Param
Function
DI1
Drive is started by closing digital input DI1 (DI=1). Switches the drive ON and START
DI2
Drive is stopped by opening digital input DI2 (DI2=0). DI2 has a higher priority than DI1, i.e. if DI2 is
open the drive can not be started. Stop the drive in according to parameter Stop-Mode and
afterwards switch the drive off.
DI3
2.01
Direction of rotation. DI3=0=forward, DI3=1=reverse
DI4
2 ramp sets selectable.
DI4=0=Ramp 1
Accel Ramp 5.09 / Decel Ramp 5.10 / Speed Reg KP 5.07 / Speed Reg TI 5.08
DI4=1=Ramp 2
Alt Accel Ramp 5.24 / Alt Decel Ramp 5.25 / Alt Speed KP 5.22 / Alt Speed TI 5.23
DI5
Emergency stop. Closed-circuit principle, must be closed for operation
DI6
Reset. Faultacknowledgement, reset faults signaled by the drive
DI7
Fixed speed 1, speed can be defined in parameter 5.13 (Ramp 5.19/5.20)
DI8
Fixed speed 2, speed can be defined in parameter 5.14 (Ramp 5.19/5.20)
DO1
6.11
Ready for On. Elektronics powered up, no fault signals present
DO2
6.12
Running. Current controller enabled
DO3
6.13
Fault signal. Converter tripped
DO4
6.14
Zero-speed signal. Motor at standstill
DO5
6.15
Main contactor on. Controlled by START command (DI1)
AI1
5.01
Speed reference
AO1
6.05
Speed actual
AO2
6.08
Armature current actual
Selection of speed reference or 2 fixed speed via DI7 and DI8
DI7
DI8
Drive is STARTed (DI1=1)
0
0
• Man Speed; Speed reference via analog input AI1
1
0
• Const Speed; Fixed speed 1, speed can be defined in parameter 5.13 (Ramp 5.19/5.20)
x
1
• Const Speed; Fixed speed 2, speed can be defined in parameter 5.14 (Ramp 5.19/5.20)
Parameter settings,
shaded areas are set by macro - all others are set during commissioning
1 - Motor Settings
2 - Operation Mode
3 - Armature
5 - Speed Controller
6 - Input/Output
1.01 Arm Cur Nom
2.01 Macro Select
[Man/Const Sp]
3.04 Arm Cur Max
5.01 Speed Ref Sel
[AI1]
6.01 AI1 Scale 100%
1.02 Arm Volt Nom
2.02 Cmd Location
[Terminals]
3.07 Torque Lim Pos
5.02 Speed Meas
Mode
6.02 AI1 Scale 0%
1.03 Field Cur Nom
2.03 Stop Mode
3.08 Torque Lim Neg
5.03 Encoder Inc
6.03 AI2 Scale 100%
1.04 Field Volt Nom
2.04 Eme Stop Mode
3.14 Cur Contr Mode
[Speed Contr]
5.09 Accel Ramp
6.04 AI2 Scale 0%
1.05 Base Speed
3.15 Torque Ref Sel
[AI2]
5.10 Decel Ramp
6.05 AO1 Assign
[Speed Act]
1.06 Max Speed
3.17 Stall Torque
5.11 Eme Stop Ramp
6.06 AO1 Mode
3.18 Stall Time
5.12 Ramp Shape
6.07 AO1 Scale 100%
5.13 Fixed Speed 1
6.08 AO2 Assign
[Arm Cur Act]
5.14 Fixed Speed 2
6.09 AO2 Mode
5.15 Zero Speed Lev
6.10 AO2 Scale 100%
5.16 Speed Level 1
6.11 DO1 Assign
[Rdy On]
5.17 Speed Level 2
6.12 DO2 Assign
[Running]
5.19 Jog Accel Ramp
6.13 DO3 Assign
[Fault]
5.20 Jog Decel Ramp
6.14 DO4 Assign
[Zero Speed]
5.21 Alt Par Sel
[DI4]
6.15 DO5 Assign
[Main Cont On]
5.24 Alt Accel Ramp
6.22 MSW Bit 11 Ass
[none]
5.25 Alt Decel Ramp
6.23 MSW Bit 12 Ass
[none]
5.26 Aux Sp Ref Sel
[Const Zero]
6.24 MSW Bit 13 Ass
[none]
6.25 MSW Bit 14 Ass
[none]