II K 4-70
Overview of Software
ParNo.
Parameter name and significance
Min
Max
Default
Unit
(1)
custom.
setting
Grp 7
Maintenance (continued)
7.15
Commis Ref 1
Commissioning reference value 1
Scaling:
Field current
0…100% = 0…4096
Torque
0…100% = 0…4096
Armature current
0…100% = 0…4096
Speed
0…max = 0…max rpm
-32768
32767
0
integer
7.16
Commis Ref 2
Commissioning reference value 2
Scaling:
Field current
0…100% = 0…4096
Torque
0…100% = 0…4096
Armature current
0…100% = 0…4096
Speed
0…max = 0…max rpm
-32768
32767
0
integer
7.17
Squarewave Per
Duration of cycle of the square-wave generator.
0.01
60.00
2.00
s
7.18
Signal
Squarewave Act
Actual value of the square-wave generator.
-
-
-
integer
7.19
Signal
Pan Text Vers
Display of text version in the control panel
integer
7.20
Signal
CPU Load
Operating performance of CPU in %
%
7.21
Signal
Con-Board
Signal which Controller Board SDCS-CON-3 is in
use.
0 = CON-3A
1..15 = unused
16 = CON-3
-
-
-
Text
(1) no changes possible if the drive is in ON-status