II K 4-69
Overview of Software
ParNo.
Parameter name and significance
Min
Max
Default
Unit
(1)
custom.
setting
Grp 7
Maintenance (continued)
7.12
Signal
Alarm Word 1
Alarm word 1. Significance of the individual bits:
All the pending alarms are displayed if the
corresponding bits are set to log. "1".
Bit
hex
Alarm
definition
00
0001
01
Parameters Added
01
0002
02
Mains Voltage Low
02
0004
03
Arm Circuit Break
03
0008
04
Converter Temp High
04
0010
05
Motor Temp High
05
0020
06
Arm Current Reduced
06
0040
07
Field Volt Limited
07
0080
08
Mains Drop Out
08
0100
09
Eme Stop Pending
09
0200
10
Autotuning Failed
10
0400
11
Comm Interrupt
11
0800
12
External Alarm
12
1000
13
ill Fieldbus Setting
13
2000
14
Up/Download Failed
14
4000
15
PanTxt Not UpToDate
15
8000
16
Par Setting Conflict
-
-
-
hex
7.13
Signal
Alarm Word 2
Alarm word 2. Significance of the individual bits:
All the pending alarms are displayed if the
corresponding bits are set to log. "1".
Bit
hex
Alarm
definition
00
0001
17
Compatibility Alarm
01
0002
18
Parameter restored
02
0004
19
-
03
0008
20
-
04
0010
21
-
05
0020
22
-
06
0040
23
-
07
0080
24
-
08
0100
25
-
09
0200
26
-
10
0400
27
-
11
0800
28
-
12
1000
29
-
13
2000
30
-
14
4000
31
-
15
8000
32
-
-
-
-
hex
7.14
Signal
Alarm Word 3
Alarm word 3. Significance of the individual bits:
All the pending alarms are displayed if the
corresponding bits are set to log. "1".
Bit
hex
Alarm
definition
00
0001
33
-
01
0002
34
-
02
0004
35
-
03
0008
36
-
04
0010
37
-
05
0020
38
-
06
0040
39
-
07
0080
40
-
08
0100
41
-
09
0200
42
-
10
0400
43
-
11
0800
44
-
12
1000
45
-
13
2000
46
-
14
4000
47
-
15
8000
48
-
-
-
-
hex
(1) no changes possible if the drive is in ON-status