II K 4-29
Overview of Software
Monitoring the Mains Voltage:
e.g.
Mains Supply Voltage
= 400 V
Application
= 4-Q
Armature Voltage Nominal = 420 V
…
with
maximum negative
settings:
Net Underv Trip (1.10) = -10%
2-Q - application
U
net
(V)
F09-Fault
level
(V)
A02-Alarm
level
(V)
U
DC
(V)
U
DC max
(V)
230
186
196
270
285
380
317
333
460
471
400
324
341
470
496
415
338
355
490
514
440
359
377
520
545
460
373
391
540
570
480
393
413
570
595
500
414
435
600
619
4-Q - application
U
net
(V)
F09-Fault
level
(V)
A02-Alarm
level
(V)
U
DC
(V)
U
DC max
(V)
230
185
194
240
255
380
308
323
400
422
400
323
339
420
444
415
331
348
430
461
440
354
372
460
489
460
370
388
480
511
480
385
404
500
533
500
400
420
520
555
Fault and Alarm Level for specified motor voltage
(U
DC
) with
Net Underv Trip (1.10) = -10%
Auto Reclosing
In parameter Net Fail Time (1.11) the maximum
tolerated mains voltage failure time is set. In case of
mains undervoltage the drive is blocked and alarm
A02 is displayed during this time. If during this time the
mains voltage returns to a voltage level higher than
the trigger level the drive restarts automatically. After
this time elapsed and the mains voltage did not return
to a voltage level higher than the trigger level the drive
stops operation and fault F09 is displayed. Auto
Reclosing is not possible in this case.
Auto Reclosing is prevented if Net Fail Time = 0,0sec
is set. In this case the drive will always stop operation
with fault message F09 displayed if mains undervolt-
age occurs.
4.5.2 Monitoring the Actual Speed Value
The speed feedback via tacho-generator or encoder
is monitored. If the deviation between the speed
calculated from the EMF and the speed feedback is
too big the drive will be switched off with a fault
message
Speed Meas Fault (F16)
.
Fault conditions:
EMF Act > 50% nominal EMF
and
Tacho Speed Act < 12.5% Base Speed (1.05)
Set
Net Underv Trip (1.10) = -10%
then
323V (Unet
min
)
is the trip level
for
F09
.
For right operation
Unet
act
has to
be
greater
than 323V.
Uarm (1.02)
= 420V
Unet
act
(1.07) = 400V
Unet
min
= 323V
= F09
Trip
F09-Mains Undervoltage
acc. to formula
Unet
min
‘ = Uarm / (1,35 x cos
α
)
Unet
min
‘ = 359V
A02-Mains Voltage Low
(5% (fix) above Unet
min
)
A02
Level
= 339V
permitted
operating
range
for Unet
359V
U
DCmax
= (U
net
*1.35 * cos
a
) - 5% Alarm level
(Mains voltage deviation is not considered.)