II K 6-35
Operating Instructions
int
e
rn
a
l
code
7.03 Diagnosis
Diagn. message
Definition /
Possible source
74
AI2 vs PTC
AI2
is set as
PTC
evaluation
and Ref-
erence
value source.
If
PTC
is allocated to
AI2
this input will
not be available
to other functions
anymore.
AI2
is normally parameter-
ized as a
reference
source for macro
1, 2, 4, 6, 7. Multiple setting is not
possible, alarm
Par Setting Conflict
(A16)
will be generated. Correct the
setting,
• set parameter
Torque Ref Sel
(3.15)
respectively
Aux Sp Ref Sel
(5.26)
from Macro depend to
Const
Zero
.
75
RecoveryTime
Recovery Time to short.
Increase
Recovery Time (3.06)
or
decrease
Arm Cur Max (3.04)
or
Overload Time (3.05)
.
76
Grp9 Disable
The digital inputs
DI1…DI4
of
macro
1, 5, 6, 7 and 8
are
re-configurable
in
parameter group
9-Macro Adapta-
tion
.
Macro 2, 3 and 4
are
not
re-
configurable. For these macros 2, 3
and 4
it is not possible to assign
any parameter in group 9. All pa-
rameters in this group
has to be
macro depend
. If there is anyone de-
fined different then macro depend
alarm
A16-Parameter Conflict
will
occur.
77-79
77…79
reserved
80
Sp Deviation
Speed does not reach setpoint
81
No Accel
Motor is not accelerating
82
SpPar Detect
Not enough measurement for the de-
tection of speed control parameters
Speed Reg KP (5.07)
and
Speed Reg
TI (5.08)
.
83-89
83…89
reserved
90
Shortcut V11
Short circuit caused by V11
91
Shortcut V12
Short circuit caused by V12
92
Shortcut V13
Short circuit caused by V13
93
Shortcut V14
Short circuit caused by V14
94
Shortcut V15
Short circuit caused by V15
95
Shortcut V16
Short circuit caused by V16
96
Result False
Result of block test unusable for a
clear diagnosis message but there is a
problem. A manual test has to be
made.
97
ShortcV15/22
Short circuit caused by V15 or V22
98
ShortcV16/23
Short circuit caused by V16 or V23
99
ShortcV11/24
Short circuit caused by V11 or V24
100
ShortcV12/25
Short circuit caused by V12 or V25
101
ShortcV13/26
Short circuit caused by V13 or V26
102
ShortcV14/21
Short circuit caused by V14 or V21
103
Ground Fault
Motor connected to ground
104
NoThyrConduc
No thyristor is conductive. Armature
winding not connected ?
int
e
rn
a
l
code
7.03 Diagnosis
Diagn. message
Definition /
Possible source
3bbbb
3bbbb
3bbbb
faulty thyristor diagnosis
(b=bridge)
3bbb
b
1…6 = thyr. V2
1
…V2
6
faulty
3bb
b
b
1…6 = thyr. V2
1
…V2
6
faulty
3b
b
bb
1…6 = thyr. V1
1
…V1
6
faulty
3
b
bbb
1…6 = thyr. V1
1
…V1
6
faulty
3
bbbb
Thyristor diagnosis “con-
ductivity test”
After test of short circuit and earth fault a conductivitiy test of all
thyristors in pairs will be done. For that purpose all bridges are
tested one after the other. A faulty result will be shown as a
number of the affected thyristors.
e.g.
two
thyristors in
one
module!
M
9
9
9
9
9
9
9
9
9
9
9
9
V25 V24
4
'LDJQRVLV
M
9
9
9
9
9
9
4
V11 V12
'LDJQRVLV
1ggnn
1ggnn
10903
faulty parameter download
(g=group, n=number)
1
0903
faulty parameter address
1
0903
Download failure
When downloading parameters from
panel to the drive the software at-
tempts to set the parameter. If the
value is actually not possible to set
(e.g. Min/Max check fails or drive is
switched on) the affected parameter
will be shown in coded form, e.g. pa-
rameter address 0903 corresponds to
9.03 (Jog 2)