Error
messages
D184B111U02 CoriolisMaster
FCM2000
97
Pos: 44.5 /Überschriften/1.1/1-spaltig/A - C/Beschreibung der Warnungen @ 11\mod_1175074174328_3101.doc @ 74685 @ 22
7.2 Description
of
the
warnings
Pos: 44.6 /Fehlermeldungen/Durchfluss/FCM2000/Warnungen Tabelle @ 11\mod_1175074674625_3101.doc @ 74747 @
Warning code and
clear text
Priority Description
Possible Causes
Corrective Measures
Warning: 1
**Simulation**
16
The Simulation is turned on
The Simulation is turned on in the
submenu Self Check
Turn off Simulation
Warning: 2
totalizer reset.
Not contained in
the fieldbus
software.
1
A totalizer was reset
Warning: 5a
Min Alarm Qm
3
The value is below the MIN Alarm
setting for Qm
The value is below the MIN Alarm
setting for Qm
Reduce the MIN Alarm
Warning: 5b
Min Alarm
5
The value is below the MIN Alarm
setting for the density
The value is below the MIN Alarm
setting for the density
Reduce the MIN Alarm
Warning: 5c
Min Alarm Temp.
7
The value is below the MIN Alarm
setting for the temperature
The value is below the MIN Alarm
setting for the temperature
Reduce the MIN Alarm
Warning: 5d
Min Alarm Conc.
The value is below the MIN Alarm
setting for the concentration.
Hystereses: ± 0.1 of selected unit.
The value is below the MIN Alarm
setting for the concentration
Reduce the MIN Alarm
Warning: 6a
Max Alarm Qm
2
The value is above the MAX Alarm
setting for Qm
The value is above the MAX
Alarm setting for Qm
Increase the MAX Alarm
Warning: 6b
Max Alarm
4
The value is above the MAX Alarm
setting for the density
The value is above the MAX
Alarm setting for the density
Increase the MAX Alarm
Warning: 6c
Max Alarm Temp.
6
The value is above the MAX Alarm
setting for the temperature
The value is above the MAX
Alarm setting for the temperature
Increase the MAX Alarm
Warning: 6d
Max Alarm Conc.
The value is above the MAX Alarm
setting for the concentration.
Hystereses: ± 0.1 of selected unit.
The value is above the MAX
Alarm setting for the concentration
Increase the MAX Alarm
Warning: 7
Ext. Data loaded
9
Is displayed for 1 minute after the
supply power is turned on
Ext. data memory (FRAM) was
replaced
Warning: 8a
Update int. data
10
Is displayed for 1 minute after the
supply power is turned on
The software was updated
Ext. data memory (FRAM) was
replaced
Warning: 8b
Update ext. data
11
Is displayed for 1 minute after the
supply power is turned on
The software was updated
Ext. data memory (FRAM) was
replaced
Warning: 9a
Overflow
→
F
Mass
12
Totalizer overflow for the forward
flow mass totalizer
Totalizer overflow for the forward
flow mass totalizer
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 9b
Overflow
←
R
Mass
13
Totalizer overflow of the mass
reverse totalizer
Totalizer overflow of the mass
reverse totalizer
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 9c
Overflow
→
F
Volume
14
Totalizer overflow for the forward
flow mass totalizer
Totalizer overflow for the forward
flow mass totalizer
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 9d
Overflow
←
R
Volume
14
Totalizer overflow for the reverse
flow volume totalizer
Totalizer overflow for the reverse
flow volume totalizer
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 9e
Overflow
→
F
%M
Totalizer overflow for the forward
flow net mass totalizer
Totalizer overflow of the forward
(oder reverse) net mass.
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 9f
Overflow
←
R
%M
Totalizer overflow for the reverse
net-mass totalizer
Totalizer overflow of the forward
(oder reverse) net mass.
Reset totalizer
Comment: Increasing the totalizer
unit increases the time between
overflows
Warning: 10
Reverse Q
17
Flowrate is in the reverse direction
Operating mode set to forward,
actual flowrate is in reverse
In Submenu „Operating mode”
change flow direction to
Forward/Reverse
Pos: 44.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 @
Summary of Contents for CoriolisMaster FCM2000
Page 112: ...Appendix 112 CoriolisMaster FCM2000 D184B111U02...
Page 113: ...Appendix D184B111U02 CoriolisMaster FCM2000 113...
Page 114: ...Appendix 114 CoriolisMaster FCM2000 D184B111U02...
Page 115: ...Appendix D184B111U02 CoriolisMaster FCM2000 115...
Page 116: ...Appendix 116 CoriolisMaster FCM2000 D184B111U02...
Page 117: ...Appendix D184B111U02 CoriolisMaster FCM2000 117...
Page 118: ...Appendix 118 CoriolisMaster FCM2000 D184B111U02...
Page 119: ...Appendix D184B111U02 CoriolisMaster FCM2000 119...
Page 120: ...Appendix 120 CoriolisMaster FCM2000 D184B111U02...