Parameterization
D184B111U02 CoriolisMaster
FCM2000
63
Pos: 41.5 /Überschriften/1.1/1-spaltig/P - R/Parameterübersicht @ 11\mod_1173965749953_3101.doc @ 72483 @ 22
6.3 Parameter
overview
Pos: 41.6 /Konfiguration, Parametrierung/Durchfluss/FCM2000/Parameterübersicht @ 7\mod_1171893992125_3101.doc @ 69108 @
Parameter
Value range / input type
Note
*Prog. level
Blocked
Technician
After pressing ENTER in the *Prog. Level* menu
the following programming levels can be selected:
"Blocked"
. Locks the unit, preventing further
entry of parameters.
"Standard":
The Standard Menu includes all the
user specific menus required for the operation of
the instrument.
"Technician":
"Technician":Expanded standard
menus with the complete set of user specific
parameters
"Service":
Additional set of Service menus only
available to ABB Automation Products Service
personnel.
If the Prog. Prot.-Code is set to 0 (default setting)
the programming levels "Standard" or
"Technician" can be accessed without entering a
code number. If any other "Progr. Prot.-Code" has
been entered (1-255) the user is asked to enter
the PP-Code after the Programming Level is
selected before the level can be opened:
Prog. Prot. Code
Technician*
****
Old Prog. Prot. (PS) code?
Technician*
After the correct code has been entered the
selected Programming Level is opened. If the
Programming Level „Service" was selected, then
the Service-Code number must be entered.
****
0 ... 9999
New Prog. Prot. (PS)
code?
Technician*
****
0 ... 9999
Language
German
Selection
English
English
The available language selections are displayed
in the 2nd line in the present language selection:
Language Version
Deutsch
German
Englisch
English
Submenu
Technician*
Mode
of
operation
The basic settings are made in this submenu.
Flow
direction
Supply/Return
Supply/Return
Table
As standard, the converter can measure flow in
both directions. It is possible to block reverse flow
measurements with this function:
Forward
Technician*
If this selection is made and the actual flow is in
the reverse direction, the flow direction arrow
←
R
in the process display (instantaneous flowrate)
blinks and the flowrate value is set to 0%. In
addition, warning 10 “Reverse Q” is displayed.
Important:
For the Operating Mode selection
Forward/Reverse the pulse output is
active for both flow directions.
Directional
display Normal
Selection
normal
Inverse
The flow direction display can be inverted. It must
be taken into consideration that the accuracy of
the flow measurement is dependent upon whether
calibration was done in the forward direction only
or in the forward and reverse direction.
Summary of Contents for CoriolisMaster FCM2000
Page 112: ...Appendix 112 CoriolisMaster FCM2000 D184B111U02...
Page 113: ...Appendix D184B111U02 CoriolisMaster FCM2000 113...
Page 114: ...Appendix 114 CoriolisMaster FCM2000 D184B111U02...
Page 115: ...Appendix D184B111U02 CoriolisMaster FCM2000 115...
Page 116: ...Appendix 116 CoriolisMaster FCM2000 D184B111U02...
Page 117: ...Appendix D184B111U02 CoriolisMaster FCM2000 117...
Page 118: ...Appendix 118 CoriolisMaster FCM2000 D184B111U02...
Page 119: ...Appendix D184B111U02 CoriolisMaster FCM2000 119...
Page 120: ...Appendix 120 CoriolisMaster FCM2000 D184B111U02...