42 Control macros
Notes
:
1)
See parameters
and
source table.
2)
Select the correct control mode from the
Motor data
view or with parameter
.
3)
PID: 0
…
10 V -> 0
…
100% PID setpoint.
4)
The signal source is powered externally. See the manufacturer’s instructions. To
use sensors supplied by the drive aux. voltage output, see connection examples of
two-wire and three-wire sensors in the hardware manual of the drive.
5)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
6)
Select the unit for analog input AI1 in the parameter
and for AI2 in the
parameter
.
Input signals
• PID set point (AI1)
• Process feedback (AI2)
• Start/stop selection (DI1)
• Internal setpoint selection 1 (DI2)
• Internal setpoint selection 2 (DI3)
• Constant speed selection 1 (DI4)
Output signals
• Digital output: Running
• Relay output: Fault(-1)
• Analog output AO: Output frequency
Source defined
DI2
Source defined
DI3
Internal setpoint active
0
0
Setpoint source: AI1 (par.
)
1
0
Internal setpoint 1 (par.
0
1
Internal setpoint 2 (par.
1
1
Internal setpoint 3 (par.
)
DI4
Operation/Parameter
Scalar control (default)
Vector control
0
Set frequency through AI1
Set speed through AI1
1