Control macros 29
Terminal sizes: 0.5 mm² … 1 mm²
Notes:
1)
In scalar control (default): See parameter group
In vector control: See parameter group
.
Select the correct control mode from the
Motor data
.
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
3)
Select voltage or current for inputs AI1 and AI2 and output AO with parameters
and
Input signals
• Analog frequency reference (AI1)
• Start/stop selection (DI1)
• Direction selection (DI2)
• Constant frequency selection (DI3)
• Constant frequency selection (DI4)
Output signals
• Digital output: Running
• Relay output: No fault [Fault (-1)]
• Analog output AO: Output frequency
DI3 DI4
Operation/Parameter
Scalar control (default)
Vector control
0
0
Set frequency through AI1
Set speed through AI1
1
0
0
1
1
1
ACS180 FW.book Page 29 Tuesday, March 9, 2021 2:25 PM