Control macros 33
Notes:
1)
Hand: 0…10 V -> frequency reference.
PID: 4…20 mA -> 0…100% PID Process feedback.
2)
The signal source is powered externally. See the manufacturer’s instructions. To
use sensors supplied by the drive aux. voltage output, see chapter
Electrical
installation
, section
Connection examples of two-wire and three-wire sensors
in the
Hardware manual
of the drive.
3)
In scalar control (default): See the
Control macros
view or
parameter group
.
4)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
5)
Select voltage or current for inputs AI1 and AI2 and output AO with parameters
and
Input signals
• Hand mode speed analog reference (AI1)
• Process feedback (AI2)
• Start/Stop selection, Hand (DI1)
• Hand(1)/PID(0) selection (DI2)
• Start/Stop selection, PID (DI3)
• Constant speed selection 1 (DI4)
Output signals
• Digital output: Running
• Relay output: Fault(-1)
• Analog output AO: Output frequency
DI4 Operation (parameter)
Scalar control (default)
0
Set frequency through AI1
1