258 Parameters
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value
used to define deceleration ramp rate (see parameter
group
). The frequency
acceleration and deceleration ramp times are therefore
related to this value (
not
to parameter
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
50.00 Hz
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The value
of this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the 16-bit scaling of power parameters. The value
of this parameter corresponds to 10000 in the fieldbus
communication. The unit is selected by parameter
.
1000.00
0.10…30000.00
Power corresponding to 10000 on fieldbus.
1 = 1 unit
Defines the 16-bit scaling of current parameters. The
value of this parameter corresponds to 10000 in fieldbus,
master/follower, etc. communication.
10000 A
0…30000 A
Current corresponding to 10000 on fieldbus.
1 = 1 A
Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A). For example, with a setting
of 500, the fieldbus reference range of 0…20000 would
correspond to a speed of 500…[
] rpm.
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 rpm
0.00 … 30000.00 rpm
Speed corresponding to minimum fieldbus reference.
1 = 1 rpm
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example, with
a setting of 30, the fieldbus reference range of 0…20000
would correspond to a speed of 30…[
Note:
This parameter is effective only with the ABB Drives
communication profile.
0.00 Hz
0.00 … 1000.00 Hz
Speed corresponding to minimum fieldbus reference.
10 = 1 Hz
Defines a filter time for signals
500 ms
2…20000 ms
Motor speed signal filter time.
1 = 1 ms
Defines a filter time for signal
.
500 ms
2…20000 ms
Output frequency signal filter time.
1 = 1 ms
Defines a filter time for signal
.
100 ms
2…20000 ms
Motor torque signal filter time.
1 = 1 ms
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 258 Tuesday, March 9, 2021 2:25 PM