198 Parameters
Displays the torque controller limitation status word.
This parameter is read-only.
-
0000h…FFFFh
Torque limitation status word.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Undervoltage
*1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum torque *1 = Torque is being limited by
or
3
Maximum torque *1 = Torque is being limited by
4
Internal current
1 = An inverter current limit (identified by bits 8…11) is active
5
Load angle
(With permanent magnet motors and reluctance motors only)
1 = Load angle limit is active, ie. the motor cannot produce any more
torque
6
Motor pullout
(With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot produce any more
torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT
*1 = Output current is being limited by a calculated thermal current
value
12
IGBT
overtemperature
*1 = Output current is being limited because of the estimated IGBT
temperature
13
IGBT overload
*1 = Output current is being limited because of the IGBT junction to
case temperature
14…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously. The bit typically
indicates the limit that is exceeded first.