Control macros 39
Default control connections for the Motor potentiometer macro
Terminal sizes: 0.5 mm² … 1 mm²
Notes
:
1)
When the input signal is on, the speed/frequency increase or decrease along a
parameter-defined change rate. See parameters
,
. If DI3 and
DI4 are both active or inactive, the frequency/speed reference is unchanged. The
existing frequency/speed reference is stored during stop and power down.
2)
In scalar control (default): See parameter group
In vector control: See parameter group
Terminals
Descriptions
Digital I/O connections
21 24 V
Aux. +24 V DC, max 200 mA
22 DGND
Aux. voltage output common
8
DI1
Start / Stop
9
DI2
Forward / Reverse
10 DI3
Speed reference up
1)
11 DI4
Speed reference down
1)
12 DCOM
Digital input common
18 DO
Running
19 DO COM
Digital output common
20 DO SRC
Digital output auxiliary voltage
Analog I/O
14 AI1/DI5
Constant speed selection 1(DI5)
2), 4)
13 AGND
Analog input circuit common
15 AI2
Not used
4)
16 AGND
Analog output circuit common
17 AO
Output frequency (0...20mA)
4)
23 10V
Ref. v10 V DC
24 SCREEN
Signal cable shield (screen)
Safe torque off (STO)
1
S+
Safe torque off function. Connected
at the factory. Drive starts only when
both circuits are closed.
2
SGND
3
S1
4
S2
Relay output
5
NC
No fault [Fault (-1)]
6
COM
7
NO
EIA-485 Modbus RTU
25 B+
Embedded Modbus RTU (EIA-485)
26 A-
27 AGND
28 SHIELD
Termination
3)
0D[RKP