234 Parameters
Defines the third underload point.
See parameter
25.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the fourth underload point.
See parameter
30.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the fifth underload point.
See parameter
30.0%
-1600.0…1600.0%
Underload point.
1 = 1%
Defines the first of the five points on the Y-axis that
together with the corresponding point on the X-axis (
37.15 ULC frequency table point 5
) define the overload (higher)
curve.
At each of the five points the value of the underload curve
point must be equal to or smaller than the value of the
overload curve point. See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the second overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the third overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the fourth overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the fifth overload point.
See parameter
.
300.0%
-1600.0…1600.0%
Overload point.
1 = 1%
Defines the time for which the monitored signal must
continuously stay above the overload curve before the
drive takes the action selected by
20.0 s
0.0…10000.0 s
Time.
1 = 1 s
Defines the time for which the monitored signal must
continuously stay below the underload curve before the
drive takes the action selected by
20.0 s
0.0…10000.0 s
Time.
1 = 1 s
No.
Name/Value
Description
Default
FbEq 16
ACS180 FW.book Page 234 Tuesday, March 9, 2021 2:25 PM