Parameters 171
Displays the ramped and shaped speed reference in rpm.
See the control chain diagram on page
This parameter is read-only.
-
-30000.00… 30000.00
rpm
Speed reference after ramping and shaping.
See par.
Selects the source that switches between the two sets of
acceleration/deceleration ramp times defined by
parameters
…
0 = Acceleration time 1, deceleration time 1 and shape
time 1 are active.
1 = Acceleration time 2, deceleration time 2 and shape
time 2 are active.
Acc/Dec time 1
0.
0
Acc/Dec time 2
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI4 (
, bit 4).
6
EFB DCU CW bit 10
Only for the DCU profile. DCU control word bit 10 received
through the embedded fieldbus interface.
20
).
-
Defines acceleration time 1 as the time required for the
speed to change from zero to the speed defined by
parameter
not
to parameter
).
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the
reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive torque limits.
3.000 s
0.000 …1800.000 s
Acceleration time 1.
10 = 1 s
No.
Name/Value
Description
Default
FbEq 16