Program features 87
Charging relay opening limit
0.73×1.41×par
value
1)
0.73×1.41 ×par
value
1)
value
1)
0.73×1.41×180 = 391
2)
0.73×1.41×440 = 453
2)
DC voltage at upper bound of
supply voltage range (
U
DCmax
)
560
648
DC voltage at lower bound of
supply voltage range (
U
DCmin
)
513
594
Charging activation/standby limit
0.73×1.41×par
value
1)
0.73×1.41×par
value
1)
value
1)
0.73×1.41×180 = 391
2)
0.73×1.41×440 = 453
2)
Undervoltage fault limit
3)
0.45×1.41×par
value
1)
0.45×1.41×par
value
1)
value
1)
0.45×1.41×180 = 241
2)
0.45×1.41×440 = 279
2)
1)
If parameter
is set to
Automatic / not selected
set to
Enable
, the value of parameter
is used,
2)
otherwise the lower
limit of the range selected with parameter
is used.
3)
The system throws an undervoltage fault when parameter
(
) elapses or the value
of parameter
is 0. In that case the standby limit is used as the undervoltage trip level. The system
throws the undervoltage fault only if the drive is modulating when the DC voltage drops below the
undervoltage trip level.
DC voltage level [V]
95.01 Supply Voltage
See
95.01
Supply voltage
.
Supply voltage range
[V]
180…415
Supply voltage
range [V]
440…480
Automatic /
Not selected