224 Parameters
Ni1000
Ni1000 sensor connected to the analog input selected by
parameter
and an analog
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
to
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along
with its temperature, the voltage over the sensor
increases. The voltage is read by the analog input and
converted into degrees.
16
PTC analog I/O
PTC sensor connected to analog input selected by
parameter
and an analog
output.
The required settings are the same as with selection
Note:
With this selection, the control program converts the
analog signal to PTC resistance value in ohms and shows
it in parameter
. The parameter name and unit still
refer to temperature.
20
Defines the fault limit for temperature supervision
function 1. The unit is selected by parameter
Note:
With a PTC sensor, the unit is ohms.
130 °C, or
266 °F or
4500 ohm
-60…5000 °C, or
-76…9032 °F, or
0...5000 ohm
Fault limit for temperature monitoring function 1.
1 = 1 unit
Defines the warning limit for temperature supervision
function 1. The unit is selected by parameter
Note:
With a PTC sensor, the unit is ohms.
110 °C, or
230 °F or
4000 ohm
-60…5000 °C, or
-76…9032 °F, or
0...5000 ohm
Warning limit for temperature monitoring function 1.
1 = 1 unit
Selects the input for parameter
, and
Not selected
None.
0
AI1 actual value
Analog input AI1.
1
AI2 actual value
Analog input AI2.
2
-
No.
Name/Value
Description
Default
FbEq 16