Parameters 127
Defines the activation delay for relay output RO1.
0.0 -
t
On
=
t
Off
0.0 … 3000.0 s
Activation delay for RO1.
10 = 1 -
Defines the deactivation delay for relay output RO1. See
parameter
.
0.0 -
0.0 … 3000.0 s
Deactivation delay for RO1.
10 = 1 -
Storage parameter for controlling the relay outputs eg.
through the embedded fieldbus interface. To control the
relay outputs (RO) of the drive, send a control word with
the bit assignments shown below as Modbus I/O data. Set
the target selection parameter of that particular data
(
. In the source
selection parameter of the desired output, select the
appropriate bit of this word.
0000h
0000h…FFFFh
RO control word.
1 = 1
Displays the number of times relay output RO1 has
changed states.
-
0…4294967000
State change count.
1 = 1
11
Configuration of the digital inputs/outputs (DIO) for use as
digital inputs,
Displays the delayed status of digital outputs DO1. This
word is updated only after activation/deactivation delays
(if any are specified).
Example:
0001 = DO1 is on.
This parameter is read-only.
-
DO1
Delayed status of digital output 1.
1 = 1
0000b…0001b
Status of digital outputs.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
Bit
Name
Description
0
RO1
Source bits for relay outputs (see parameter
8
DO1
ACS180 FW.book Page 127 Tuesday, March 9, 2021 2:25 PM