Parameters 243
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
21
Supervision 2
Bit 1 of
22
Supervision 3
Bit 2 of
23
).
-
Defines a deadband around the setpoint. Whenever
process feedback enters the deadband, a delay timer
starts. If the feedback remains within the deadband longer
than the delay (
), the PID
controller output is frozen. Normal operation resumes
after the feedback value leaves the deadband.
0.0
0……200000.0
Deadband range.
1 = 1
Delay for the deadband. See parameter
0.0 s
0.0 … 3600.0 s
Delay for deadband area.
1 = 1 s
Defines the start limit for the sleep function. If the value is
0.0, set 1 sleep mode is disabled.
The sleep function compares the motor speed to the value
of this parameter. If the motor speed remains below this
value longer than the sleep delay defined by
, the drive enters the sleep mode and stops the
motor.
0.0
0.0…200000.0
Sleep start level.
1 = 1
Defines a delay before the sleep function actually
becomes enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is enabled by
parameter
, and resets when the
sleep mode is disabled.
60.0 s
0.0…3600.0 s
Sleep start delay.
1 = 1 s
No.
Name/Value
Description
Default
FbEq 16
Setpoint
Time
Feedback
PID controller
output
PID controller
output frozen