Parameters 273
Displays status information on process external PID
control.
This parameter is read-only.
-
0000h…FFFFh
Process PID control status word.
1 = 1
See parameter
See parameter
See parameter
.
0.000 s
Defines, together with parameter
, a
general scaling factor for the external PID control chain.
The scaling can be utilized when, for example, the
process setpoint is input in Hz, and the output of the PID
controller is used as an rpm value in speed control. In this
case, this parameter might be set to 50, and parameter
to the nominal motor speed at 50 Hz.
In effect, the output of the PID controller [
] when
deviation (setpoint - feedback) = [
] and [
] = 1.
Note:
The scaling is based on the ratio between
and
. For example, the values 50 and 1500 would
produce the same scaling as 1 and 3.
1500.00
-200000.00...
200000.00
Process setpoint base.
1 = 1
See parameter
1500.00
-200000.00...
200000.00
Process PID controller output base.
1 = 1
See parameter
See parameter
.
See parameter
.
See parameter
0.00 PID
customer
units
See parameter
0.00 PID
customer
units
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Value
0
PID active
1 = Process PID control active.
1
Reserved
2
Output frozen
1 = Process PID controller output frozen. Bit is set if parameter
is TRUE, or the deadband function is
active (bit 9 is set).
3…6
Reserved
7
Output limit high
1 = PID output is being limited by par.
8
Output limit low
1 = PID output is being limited by par.
9
Deadband active
1 = Deadband is active.
10…11 Reserved
12
Internal setpoint
active
1 = Internal setpoint active (see par.
…
13…15 Reserved