Installation 95
Default I/O connection diagram
XPOW
External power input
24 V DC, 1.6 A
+24VI
1
GND
2
XRO1, XRO2
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
NO
1
COM
2
NC
3
Relay output RO2 [Fault(-1)]
250 V AC / 30 V DC
2 A
NO
4
COM
5
NC
6
XD24
+24 V DC*
+24VD
1
Digital input ground
DIGND
2
+24 V DC*
+24VD
3
Digital input/output ground
DIOGND
4
Ground selection jumper
AI1
XDI
Digital input DI1 [Stop/Start]
DI1
1
Digital input DI2 [Constant speed 1]
DI2
2
Digital input DI3 [Reset]
DI3
3
Digital input DI4
DI4
4
Digital input DI5 [EXT1/EXT2 selection]
DI5
5
Start interlock (0 = Stop)
DIIL
A
XDIO
Digital input/output DIO1 [Output: Ready]
DIO1
1
Digital input/output DIO2 [Output: Running]
DIO2
2
XAI
Reference voltage (+)
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analog input AI1 (Current or voltage, selectable by
jumper AI1) [Current] [Speed reference 1]
AI1+
4
AI1-
5
Analog input AI2 (Current or voltage, selectable by
jumper AI2) [Current] [Process actual value 1]
AI2+
6
AI2-
7
AI1 current/voltage selection jumper
AI1
AI2 current/voltage selection jumper
AI2
XAO
Analog output AO1 [Current]
AO1+
1
AO1-
2
Analog output AO2 [Speed rpm]
AO2+
3
AO2-
4
XD2D
Drive-to-drive link termination jumper
T
Drive-to-drive link.
B
1
A
2
BGND
3
XSTO
Safe torque off. Both circuits must be closed for the
drive to start.
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
Notes:
[…] denotes default setting with ACQ810
standard pump control program (
Factory
defs
macro). See
Firmware manual
for
other macros.
*Total maximum current: 200 mA
The wiring shown is for demonstrative
purposes only. Further information of the
usage of the connectors and jumpers are
given in the text; see also chapter
Wire sizes and tightening torques:
XPOW, XRO1, XRO2, XD24:
0.5 … 2.5 mm
2
(24…12 AWG). Torque:
0.5 N·m (5 lbf·in)
XDI, XDIO, XAI, XAO, XD2D, XSTO:
0.5 … 1.5 mm
2
(28…14 AWG). Torque:
0.3 N·m (3 lbf·in)
XPOW
(2-pole, 2.5 mm
2
)
Order of terminal headers and
jumpers
XRO1
(3-pole, 2.5 mm
2
)
XRO2
(3-pole, 2.5 mm
2
)
XD24
(4-pole, 2.5 mm
2
)
XDI
(6-pole, 1.5 mm
2
)
DI/DIO grounding selection
XDIO
(2-pole, 1.5 mm
2
)
XAI
(7-pole, 1.5 mm
2
)
AI1, AI2
XAO
(4-pole, 1.5 mm
2
)
XD2D
(3-pole, 1.5 mm
2
)
XSTO (orange)
(4-pole, 1.5 mm
2
)
T
Summary of Contents for ACQ810-04
Page 4: ......
Page 10: ...10 ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Planning the cabinet installation ...
Page 75: ...Installation 75 Assembly drawing frame G1 ...
Page 76: ...76 Installation Assembly drawing frame G2 ...
Page 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Page 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Page 100: ...100 Installation ...
Page 104: ...104 Installation checklist ...
Page 106: ...106 Start up ...
Page 108: ...108 Fault tracing ...
Page 128: ...128 Technical data ...
Page 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Page 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 132: ...132 Dimension drawings ...
Page 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Page 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 136: ...136 Dimension drawings ...
Page 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 138: ...138 Dimension drawings Bottom plate ...
Page 142: ...142 du dt filters ...
Page 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...