Planning the electrical installation 47
Additional requirements for high-output motors and IP23 motors
If you will use a motor with the rated output power higher than what is stated for the
particular frame size in EN 50347 (2001), or if the degree of protection is IP23, follow
these guidelines when defining the protection of the motor:
•
The table below shows the requirements for ABB random-wound motor series (for
example, M3AA, M3AP and M3BP).
•
The table below shows the requirements for random-wound and form-wound non-ABB
motors with
P
N
< 350 kW. For motors with
P
N
> 350 kW, consult the motor
manufacturer.
Nominal AC line
voltage)
Requirement for
Motor
insulation
system
ABB d
u
/d
t
and
common mode filters,
insulated N-end motor
bearings
100 kW <
P
N
< 200 kW
P
N
> 200 kW
140 hp <
P
N
< 268 hp
P
N
> 268 hp
U
N
< 500 V
Standard
+ N
+ N + CMF
500 V <
U
N
< 600 V Standard
+ d
u
/d
t
+ N
+ d
u
/d
t
+ N + CMF
or
Reinforced
+ N
+ N + CMF
600 V <
U
N
< 690 V Reinforced
+ d
u
/d
t
+ N
+ d
u
/d
t
+ N + CMF
Nominal AC line
voltage
Requirement for
Motor insulation
system
ABB d
u
/d
t
and common mode
filters, insulated N-end motor
bearings
100 kW <
P
N
< 350 kW or
IEC 315 < frame size < IEC 400
134 hp <
P
N
< 469 hp or
NEMA 500 < frame size <
NEMA 580
U
N
< 420 V
Standard:
Û
LL
=
1300 V
+ N + CMF
420 V <
U
N
< 500 V Standard:
Û
LL
=
1300 V
+ d
u
/d
t
+ N + CMF
or
Reinforced:
Û
LL
=
1600 V, 0.2
microsecond rise
time
+ N + CMF
500 V <
U
N
< 600 V Reinforced:
Û
LL
=
1600 V
+ d
u
/d
t
+ N + CMF
or
Reinforced:
Û
LL
=
1800 V
+ N + CMF
600 V <
U
N
< 690 V Reinforced:
Û
LL
=
1800 V
+ d
u
/d
t
+ N + CMF
Reinforced:
Û
LL
=
2000 V, 0.3
microsecond rise
time ***
N + CMF
Summary of Contents for ACQ810-04
Page 4: ......
Page 10: ...10 ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Planning the cabinet installation ...
Page 75: ...Installation 75 Assembly drawing frame G1 ...
Page 76: ...76 Installation Assembly drawing frame G2 ...
Page 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Page 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Page 100: ...100 Installation ...
Page 104: ...104 Installation checklist ...
Page 106: ...106 Start up ...
Page 108: ...108 Fault tracing ...
Page 128: ...128 Technical data ...
Page 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Page 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 132: ...132 Dimension drawings ...
Page 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Page 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 136: ...136 Dimension drawings ...
Page 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 138: ...138 Dimension drawings Bottom plate ...
Page 142: ...142 du dt filters ...
Page 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...