Planning the electrical installation 51
Alternative power cable types
The power cable types that can be used with the drive are represented below.
Motor cable shield
If the motor cable shield is used as the sole protective earth conductor of the motor,
ensure that the conductivity of the shield is sufficient. See subsection
above,
or IEC 60439-1. To effectively suppress radiated and conducted radio-frequency
emissions, the shield conductivity must be at least 1/10 of the phase conductor
conductivity. The requirements are easily met with a copper or aluminium shield. The
minimum requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape or copper wire. The
better and tighter the shield, the lower the emission level and bearing currents.
Recommended:
Symmetrical shielded cable: three phase conductors and a concentric or
otherwise symmetrically constructed PE conductor, and a shield
PE conductor
and shield
Shield
Shield
Note:
A separate PE conductor is
required if the conductivity of the
cable shield is < 50 % of the
conductivity of the phase
conductor.
PE
PE
Shield
PE
Not allowed for motor cabling
: A four-conductor system (three phase conductors and a
protective conductor)
Not allowed for input or motor cabling:
Symmetrical cable with individual shields for each phase
conductor
Shield
PE
Insulation jacket
Copper wire screen
Helix of copper tape
or copper wire
Cable core
Inner insulation
Summary of Contents for ACQ810-04
Page 4: ......
Page 10: ...10 ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Planning the cabinet installation ...
Page 75: ...Installation 75 Assembly drawing frame G1 ...
Page 76: ...76 Installation Assembly drawing frame G2 ...
Page 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Page 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Page 100: ...100 Installation ...
Page 104: ...104 Installation checklist ...
Page 106: ...106 Start up ...
Page 108: ...108 Fault tracing ...
Page 128: ...128 Technical data ...
Page 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Page 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 132: ...132 Dimension drawings ...
Page 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Page 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 136: ...136 Dimension drawings ...
Page 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 138: ...138 Dimension drawings Bottom plate ...
Page 142: ...142 du dt filters ...
Page 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...