122 Technical data
Electrical power network specification
Voltage (
U
1
)
380...500 VAC 3-phase
± 10%
Rated conditional short-
circuit current (IEC 60439-1)
65 kA when protected by fuses given in the fuse tables
Frequency
48 to 63 Hz, maximum rate of change 17%/s
Imbalance
Max.
± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection data
Motor types
Asynchronous AC induction motors
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical, U
max
at the field weakening point
Frequency
DTC mode: 0 to 3.2 ·
f
f
. Maximum frequency 500 Hz (120 Hz with d
u
/d
t
or
sine filter). Low motor noise mode is recommended with high frequencies
(see also
Firmware manual
).
f
f
=
f
f
: frequency at field weakening point;
U
N
: electrical power system voltage;
U
m
: rated motor voltage;
f
m
: rated motor frequency
Frequency resolution
0.01 Hz
Current
See section
Field weakening point
0…500 Hz
Switching frequency
3 kHz (typically)
Maximum recommended
motor cable length
DTC control
Scalar control
300 m (984 ft)
300 m (984 ft)
Note
: Motor cable longer than 100 m (328 ft) is allowed but then the EMC
Directive requirements of Category C3 may not be fulfilled.
Control unit (JCU-21) connection data
Power supply
24 V (±10%) DC, 1.6 A
Supplied from the power unit of the drive, or from an external power supply
through connector XPOW (pitch 5 mm, wire size 2.5 mm
2
).
Relay outputs RO1…RO2
(XRO1 … XRO2)
Connector pitch 5 mm, wire size 2.5 mm
2
250 V AC / 30 V DC, 2 A
Protected by varistors
Note:
At installation sites between 2000 meters (6562 feet) and 4000 meters
(13123 feet), the Protective Extra Low Voltage (PELV) requirements are not
fulfilled if a relay output is used with a voltage greater than 48 V.
+24 V output
(XD24)
Connector pitch 5 mm, wire size 2.5 mm
2
Digital inputs DI1…DI5
(XDI:1 … XDI:5)
Connector pitch 3.5 mm, wire size 1.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP (DI1…DI4), NPN (DI5)
Filtering: 0.25 ms
DI5 (XDI:5) can alternatively be used as an input for 1…3 PTC thermistors.
“0” > 4 kohm, “1” < 1.5 kohm
I
max
: 15 mA
Start interlock input DIIL
(XDI:A)
Wire size 1.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP
Filtering: 0.25 ms
U
N
U
m
·
f
m
Summary of Contents for ACQ810-04
Page 4: ......
Page 10: ...10 ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Planning the cabinet installation ...
Page 75: ...Installation 75 Assembly drawing frame G1 ...
Page 76: ...76 Installation Assembly drawing frame G2 ...
Page 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Page 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Page 100: ...100 Installation ...
Page 104: ...104 Installation checklist ...
Page 106: ...106 Start up ...
Page 108: ...108 Fault tracing ...
Page 128: ...128 Technical data ...
Page 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Page 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 132: ...132 Dimension drawings ...
Page 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Page 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 136: ...136 Dimension drawings ...
Page 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 138: ...138 Dimension drawings Bottom plate ...
Page 142: ...142 du dt filters ...
Page 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...