50 Planning the electrical installation
Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper shield for
the drives with nominal current. See also
Terminal and lead-through data for the power
on page
121.
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three
ladder type trays one on top of the other, ambient temperature 30 °C (86
°
F) PVC
insulation, surface temperature 70 °C (158
°
F) (EN 60204-1 and IEC 60364-5-52). For
other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive
.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other conditions,
dimension the cables according to local safety regulations, appropriate input voltage
and the load current of the drive.
ACQ810-04
IEC
1)
US
2)
Cu cable type Al cable type
Cu cable type
Al cable type
mm
2
mm
2
AWG/kcmil
AWG/kcmil
-377A-4
2 × (3×120)
3 × (3×120)
2 × 250 MCM
2 × 350 MCM
-480A-4
3 × (3×95)
3 × (3×150)
2 × 500 MCM or 3 × 250 MCM 2 × 600 MCM or 3 × 300 MCM
-570A-4
3 × (3×120)
3 × (3×185)
2 × 500 MCM or 3 × 250 MCM 2 × 700 MCM or 3 × 350 MCM
-634A-4
3 × (3×150)
3 × (3×240)
2 × 600 MCM or 3 × 300 MCM 3 × 400 MCM or 4 × 250 MCM
-700A-4
3 × (3×185)
4 × (3×185)
2 × 700 MCM or 3 × 350 MCM 3 × 500 MCM or 4 × 300 MCM
-785A-4
3 × (3×240)
4 × (3×240)
3 × 500 MCM or 4 × 300 MCM 3 × 600 MCM or 4 × 400 MCM
-857A-4
3 × (3×240)
4 × (3×240)
3 × 500 MCM or 4 × 300 MCM 3 × 700 MCM or 4 × 500 MCM
3BFA 01051905 D
Summary of Contents for ACQ810-04
Page 4: ......
Page 10: ...10 ...
Page 22: ...22 Introduction to the manual ...
Page 42: ...42 Planning the cabinet installation ...
Page 75: ...Installation 75 Assembly drawing frame G1 ...
Page 76: ...76 Installation Assembly drawing frame G2 ...
Page 83: ...Installation 83 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 84: ...84 Installation Assembly drawing of installing the drive module to the cabinet frame G1 ...
Page 85: ...Installation 85 Assembly drawing of installing the drive module to the cabinet frame G2 ...
Page 100: ...100 Installation ...
Page 104: ...104 Installation checklist ...
Page 106: ...106 Start up ...
Page 108: ...108 Fault tracing ...
Page 128: ...128 Technical data ...
Page 130: ...130 Dimension drawings Frame G1 Drive module dimensions ...
Page 131: ...Dimension drawings 131 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 132: ...132 Dimension drawings ...
Page 133: ...Dimension drawings 133 Frame G1 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 134: ...134 Dimension drawings Frame G2 Drive module dimensions ...
Page 135: ...Dimension drawings 135 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 136: ...136 Dimension drawings ...
Page 137: ...Dimension drawings 137 Frame G2 Cabling panels H381 installed into a Rittal TS 8 cabinet ...
Page 138: ...138 Dimension drawings Bottom plate ...
Page 142: ...142 du dt filters ...
Page 144: ...3AUA0000120538 Rev A EN 2012 06 27 Contact us www abb com drives www abb com drivespartners ...