Functional Description of the Ethernet Modules
6-3
6.1.2
Installing an Ethernet module
When plugging an Ethernet module into the AC 800F for the first time, note that there
may be electrostatic discharge from the module which may cause malfunctions of the
AC 800F electronics.
To avoid damage resulting from ESD, proceed as described below when in-
stalling or replacing a module. Note that this procedure is mandatory:
1. Make sure that the AC 800F is switched off.
If required, switch off the AC 800F.
2. Remove either the already installed board to be replaced or the cap (dummy
panel) from the appropriate slot.
3. Establish a good electrical contact between a passive part of the housing and the
special ESD protection bag in which the module has been delivered to you.
4. Take the Ethernet module out of the ESD protection bag. Do not touch the board
components. Only touch the module front panel.
5. Carefully insert the Ethernet module into the appropriate slot E1 or E2. Touch the
AC 800F housing either while inserting the module into the slot or at least directly
prior to inserting it in order to provide for discharge.
There are contacts on the upper and lower edge of the board which act as high-
resistance bridges towards the housing. This eliminates residual charges that may
still exist and avoids electromagnetic interference.
6. Hand-tighten the screws on the module front panel top and bottom. Only then it
can be guaranteed that the specified EMC requirements values are met.
7. Lock the slide-lock to cover
the upper locking screw. Use
an appropriate tool to slide the
lock to the left hand side until
the screw head is completely
covered and the Lock inscrip-
tion is visible.
Fig. 6-1
Locking the module slide lock
Only when the module has been plugged in and locked properly, it will be switched
on and identified.
8. Make the Ethernet cabling.
9. Switch on the AC 800F.
Summary of Contents for AC 800F
Page 1: ... PROCESS AUTOMATION Freelance 2019 Mounting and Installation Instructions AC 800F Controller ...
Page 2: ......
Page 66: ...3 Mounting the AC 800F 3 38 ...
Page 168: ...4 Cabling the AC 800F 4 102 ...
Page 290: ...7 Functional Description of the Fieldbus Modules 7 36 ...
Page 317: ...10 Approvals certificates 10 1 10 Approvals certificates 10 1 ISO 9001 Fig 10 1 ISO 9001 ...
Page 318: ...10 Approvals certificates 10 2 Fig 10 2 ISO 9001 ...
Page 319: ...10 Approvals certificates 10 3 Fig 10 3 ISO 9001 ...
Page 320: ...10 Approvals certificates 10 4 Fig 10 4 ISO 9001 ...
Page 321: ...10 Approvals certificates 10 5 10 2 ISO 9000 Fig 10 5 ISO 9000 ...
Page 322: ...10 Approvals certificates 10 6 Fig 10 6 ISO 9000 ...
Page 323: ...10 Approvals certificates 10 7 10 3 CE Fig 10 7 CE certificate page 1 ...
Page 324: ...10 Approvals certificates 10 8 Fig 10 8 CE certificate page 2 ...
Page 325: ...10 Approvals certificates 10 9 Fig 10 9 CE certificate page 3 ...
Page 326: ...10 Approvals certificates 10 10 Fig 10 10CE certificate supplement ...
Page 327: ...10 Approvals certificates 10 11 10 4 CSA Fig 10 11 CSA certificate page 1 ...
Page 328: ...10 Approvals certificates 10 12 Fig 10 12 CSA certificate page 2 ...
Page 329: ...10 Approvals certificates 10 13 Fig 10 13 CSA certificate page 3 ...
Page 330: ...10 Approvals certificates 10 14 Fig 10 14 CSA certificate page 4 ...
Page 331: ...10 Approvals certificates 10 15 10 5 UL Fig 10 15 UL certificate ...
Page 332: ...10 Approvals certificates 10 16 Fig 10 16 UL certificate page 2 ...
Page 333: ...10 Approvals certificates 10 17 Fig 10 17 UL certificate page 3 ...
Page 334: ...10 Approvals certificates 10 18 Fig 10 18 UL certificate page 4 ...
Page 335: ...10 Approvals certificates 10 19 10 6 GUS certificate Fig 10 19 GUS certificate ...
Page 369: ...13 Glossary 13 18 Component of the Freelance 2000 System ...
Page 378: ......