AC 800F Functional Description
5-6
Technical data of SA 811F (preliminary)
Input voltage
115 - 230 V AC, perm. range 90 ... 260 V AC
Mains frequency
50 - 60 Hz, perm. range 47 ... 63 Hz
Protection against polarity reversal
AC power supply, therefore not applicable
Protection against improper voltage
values and/or frequency
application of voltages below nominal
voltage does not cause destruction, DC
supply possible
Bridging time in case of power failure
> 20 ms without malfunctions
Fuse
subminiature fuse, type 2.5 AT in input
circuit
Output voltages
3.3 V DC (
±
3 %), 5.0 V DC (
±
3 %)
Output current
0.5 ... 6.5 A to 3.3 V and
0.5 ... 5.5 A to 5.0 V
Total output power
max. 35 W
Current limiting
approximately 7.5 A, automatic restart of
normal operation
Input current at nominal load
230 V AC: 275 mA
115 V AC: 541 mA
Rated input power
63 VA
Inrush current
max.15 times the peak value of the nominal
current (NAMUR)
Power factor
230 V: around 72 %
115 V: around 74 %
Efficiency
230 V: around 77 %
115 V: around 76 %
Thermal power loss with nominal load
9.9 W
Weight
460 g
Connectors
Power connector
Diagnostic interface
Module/CPU board
G30E3M (from Hirschmann)
9-pin Sub-D connector (male)
96-pin connector
Test voltage (routine check test)
3.3 kV DC primary/secondary,
3.3 kV DC primary/housing
Safety low voltage on the output
yes, SELV
Protective separation from other circuits yes, according to IEC 60364-4-41/ 10.92
and DIN VDE 0106 Part 101/11.86
(replaced with EN 61140/08.2001 and EN
60947/12.99), safety transformer to
DIN VDE 0551 Part 1 and EN60742
EEPROM
serial, 512 bytes, 10
7
write cycles
For more detailed information please refer to Section 9, Technical data.
Summary of Contents for AC 800F
Page 1: ... PROCESS AUTOMATION Freelance 2019 Mounting and Installation Instructions AC 800F Controller ...
Page 2: ......
Page 66: ...3 Mounting the AC 800F 3 38 ...
Page 168: ...4 Cabling the AC 800F 4 102 ...
Page 290: ...7 Functional Description of the Fieldbus Modules 7 36 ...
Page 317: ...10 Approvals certificates 10 1 10 Approvals certificates 10 1 ISO 9001 Fig 10 1 ISO 9001 ...
Page 318: ...10 Approvals certificates 10 2 Fig 10 2 ISO 9001 ...
Page 319: ...10 Approvals certificates 10 3 Fig 10 3 ISO 9001 ...
Page 320: ...10 Approvals certificates 10 4 Fig 10 4 ISO 9001 ...
Page 321: ...10 Approvals certificates 10 5 10 2 ISO 9000 Fig 10 5 ISO 9000 ...
Page 322: ...10 Approvals certificates 10 6 Fig 10 6 ISO 9000 ...
Page 323: ...10 Approvals certificates 10 7 10 3 CE Fig 10 7 CE certificate page 1 ...
Page 324: ...10 Approvals certificates 10 8 Fig 10 8 CE certificate page 2 ...
Page 325: ...10 Approvals certificates 10 9 Fig 10 9 CE certificate page 3 ...
Page 326: ...10 Approvals certificates 10 10 Fig 10 10CE certificate supplement ...
Page 327: ...10 Approvals certificates 10 11 10 4 CSA Fig 10 11 CSA certificate page 1 ...
Page 328: ...10 Approvals certificates 10 12 Fig 10 12 CSA certificate page 2 ...
Page 329: ...10 Approvals certificates 10 13 Fig 10 13 CSA certificate page 3 ...
Page 330: ...10 Approvals certificates 10 14 Fig 10 14 CSA certificate page 4 ...
Page 331: ...10 Approvals certificates 10 15 10 5 UL Fig 10 15 UL certificate ...
Page 332: ...10 Approvals certificates 10 16 Fig 10 16 UL certificate page 2 ...
Page 333: ...10 Approvals certificates 10 17 Fig 10 17 UL certificate page 3 ...
Page 334: ...10 Approvals certificates 10 18 Fig 10 18 UL certificate page 4 ...
Page 335: ...10 Approvals certificates 10 19 10 6 GUS certificate Fig 10 19 GUS certificate ...
Page 369: ...13 Glossary 13 18 Component of the Freelance 2000 System ...
Page 378: ......