5
AC 800F Functional Description
5-34
You can skip the error message by pressing the Esc key, and restart the 1
st
Stage
self-test. The message “
n times skipped
“ indicates how often the error has already
been ignored. If the error cause still exists or another error should occur, an error
entry is written into the error memory, until the max. error count is reached.
The
maximum
error
count
has
been
reached:
further
operation
rejected
!!! Please, contact service !!!
Once the error memory is full, further operation of the AC 800F is disabled. Please
contact the service in this case.
5.4.4
Configuring the Boot Loader
When the
1
st
Stage has been completed without any errors, the Boot Loaderis
started. If you should like to modify the Boat Loader configuration, the Run/Stop
switch must be in the Stop position. In the Run position no user settings can be
made, and not all configuration messages are output. The EPROM version number
is shown in the Boot Loader header. When the Run/Stop switch is in the Stop
position, the current parameters are output after this. These parameters can be
modified by pressing any key during the waiting time to call the input menu.
ABB
** AC800F **
Fieldcontroller BootLoader V6.80
(C)1999 ABB
Automation Products
17 May 2001
T.Guenther
Testing network connection 1 ... Ok
Testing network connection 2 ... Error: Controller or network problem: 80000386
------------------------------------------------------------------------------
CPU is i960HT [B0/B1] with 4 MByte RAM
System will startup in AUTO mode
First Network interface [00:C0:C9:10:00:88] - Cheapernet
- IP address:
172.16.1.1
- Subnet mask: 255.255.240.0
Second Network interface [00:C0:C9:10:00:A1] - Cheapernet
- IP address:
172.16.16.1
- Subnet mask: 255.255.240.0
Default router: 0.0.0.0
RTC-Time:
17.05.01, 00:05:13 local
------------------------------------------------------------------------------
To change these parameters, hit <SPACE> within 2 seconds
Fig. 5-19
Boot Loader system messages up to the key prompt
Summary of Contents for AC 800F
Page 1: ... PROCESS AUTOMATION Freelance 2019 Mounting and Installation Instructions AC 800F Controller ...
Page 2: ......
Page 66: ...3 Mounting the AC 800F 3 38 ...
Page 168: ...4 Cabling the AC 800F 4 102 ...
Page 290: ...7 Functional Description of the Fieldbus Modules 7 36 ...
Page 317: ...10 Approvals certificates 10 1 10 Approvals certificates 10 1 ISO 9001 Fig 10 1 ISO 9001 ...
Page 318: ...10 Approvals certificates 10 2 Fig 10 2 ISO 9001 ...
Page 319: ...10 Approvals certificates 10 3 Fig 10 3 ISO 9001 ...
Page 320: ...10 Approvals certificates 10 4 Fig 10 4 ISO 9001 ...
Page 321: ...10 Approvals certificates 10 5 10 2 ISO 9000 Fig 10 5 ISO 9000 ...
Page 322: ...10 Approvals certificates 10 6 Fig 10 6 ISO 9000 ...
Page 323: ...10 Approvals certificates 10 7 10 3 CE Fig 10 7 CE certificate page 1 ...
Page 324: ...10 Approvals certificates 10 8 Fig 10 8 CE certificate page 2 ...
Page 325: ...10 Approvals certificates 10 9 Fig 10 9 CE certificate page 3 ...
Page 326: ...10 Approvals certificates 10 10 Fig 10 10CE certificate supplement ...
Page 327: ...10 Approvals certificates 10 11 10 4 CSA Fig 10 11 CSA certificate page 1 ...
Page 328: ...10 Approvals certificates 10 12 Fig 10 12 CSA certificate page 2 ...
Page 329: ...10 Approvals certificates 10 13 Fig 10 13 CSA certificate page 3 ...
Page 330: ...10 Approvals certificates 10 14 Fig 10 14 CSA certificate page 4 ...
Page 331: ...10 Approvals certificates 10 15 10 5 UL Fig 10 15 UL certificate ...
Page 332: ...10 Approvals certificates 10 16 Fig 10 16 UL certificate page 2 ...
Page 333: ...10 Approvals certificates 10 17 Fig 10 17 UL certificate page 3 ...
Page 334: ...10 Approvals certificates 10 18 Fig 10 18 UL certificate page 4 ...
Page 335: ...10 Approvals certificates 10 19 10 6 GUS certificate Fig 10 19 GUS certificate ...
Page 369: ...13 Glossary 13 18 Component of the Freelance 2000 System ...
Page 378: ......