Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
91
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Enter a brief text description for the output group.
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
To add a new output group:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Output groups.
A list of the available output groups is displayed.
3. Press F3 (Search), and then enter a number for the new output group that
you want to add.
Press the jog dial to confirm the entry.
4. Select the output group type (PRG, EXTIN, SND, FR, or FP).
5. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
6. Enter a brief text description for the output group.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Output group activation
Output groups can be activated by any of the following:
•
Zone activation with delays
•
Output group confirmation for specific outputs (EN 54-2 type C)
•
Logic rules (configured via the configuration utility PC application)
•
Manual activation by programmable start/stop buttons (evacuation panels
only)
To avoid unexpected alarm behaviour, consider the activation options when
configuring your fire system. If zone activation is not programmed correctly then
a zone in alarm could override any required confirmation configuration of an
output group.
Delayed output group activation with alarm confirmation
Note:
This option is compliant with EN 54 type C alarm confirmation.
Activation of control panel output groups can be delayed based on alarm
confirmation configuration (this may be used, for example, with outputs for
extinguishing devices). The maximum configurable delay is 999 seconds.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......