Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
57
Firenet opmode
Available network operation modes are shown below.
Table 23: Firenet operation modes
Mode
Description
Stand-alone
Configures a stand-alone control panel. This is the default setting for fire
alarm control panels.
Networked
Configures a networked control panel. See description below.
Repeater
Configures a networked repeater. This is the default setting for repeater
panels. See description below.
In networked mode, the control panel uses the network to process and show the
alarm and fault events received from any remote panel which belong to any of
the local zones in the system.
In repeater mode, in addition to having the network panel functionality described
above, the panel indicates all events for all panels selected to be repeated or as
defined by the event filter configuration. For example, if the control panel event
filter has condition and fault reporting disabled, the repeater repeats only alarm,
prealarm, alert, and technical alarm conditions.
Therefore, in Repeater mode the panel uses the network:
•
To process and display the events received from any remote panel that affect
the local zones in the system
•
To display any event coming from any of the remote panels present in the
repeated panel map (or as defined by the event filter configuration)
To change the network operation mode settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Firenet Opmode.
3. Select Standalone, Networked, or Repeater).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
A stand-alone panel retains its network node even though it is not communicating
with the network.
Repeater map
The default setting is YES (all control panels in the fire network are repeated).
To change the repeater map settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Repeater map.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......