Chapter 2: Installation
ZP2 Series Installation Manual
33
Ring configuration
Ring network configuration is recommended as it provides for redundancy in the
transmission path.
For ring configuration (Class A), use both ports to connect all network boards or
control panels to form a ring, as shown below.
Figure 18: Fire network ring configuration
Bus configuration
Caution:
Use bus network configuration only in cases where the detection zones
and mandatory EN 54-2 output functions (sounder and fire routing outputs) are
not remote between panels.
Bus network configuration is not recommended. It does not provide for
redundancy in the transmission path and creates a fire network much more
sensitive to faults.
For bus configuration (Class B), connect control panels as shown below.
Figure 19: Fire network bus configuration
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......