Chapter 3: Configuration and commissioning
96
ZP2 Series Installation Manual
Notes
•
Global delay options only set the delays of the zones that are enabled to
activate the sounder or fire routing group. For example, if sounders and fire
routing activate for zone 1 with a delay of 10 seconds and for zone 5 with a
delay of 2 minutes, when selecting this option, sounders and fire routing will
activate with the same selected delay after alarms in zones 1 or 5 and will not
activate for all the other zones.
•
The Activate for all zones option allows the user to apply the delay to all
zones (including those previously configured not to activate the output group).
Per zone (sounder, fire routing, fire protection, or program)
Select Per zone to activate output groups with different delays (including no
activation) depending on which zone generated the alarm.
All outputs assigned to the output group activate depending on alarms in the fire
network, in the local range of zones of the panel, and with different delays.
For example, select this option to activate output group number 5 (sounder, fire
routing, fire protection, or program) with a delay of 10 seconds for a detector
alarm in zone 1 and with a delay of 2 minutes for a detector alarm in zone 5.
To configure per zone delay options:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select Per zone.
3. Select the zone, and then select the output group whose delay you want to
configure for the selected zone.
The corresponding output group configuration options for the selected zone
are displayed on the screen.
4. Select Active, and then select YES or NO to define output group activation for
the zone.
5. Enter the required delay in minutes and seconds.
The maximum delay value for sounder, fire routing, and fire protection output
groups is 10 minutes. The maximum delay value for program output groups is
16 minutes and 40 seconds.
6. If required, enter a warning delay (in minutes and seconds) for sounder output
groups in applications using warning tones (second stage sounders).
A warning delay is only observed if the corresponding warning time is also
configured (see “Warning time” on page 100 for more information on this
option). The maximum warning delay value is 10 minutes.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......