Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
101
There are three configurable time periods, as shown in the table below.
Table 59: Warning time, warning delay, and delay
Time period
Description
Warning time
The time from when the alarm is reported until the sounders activate
the evacuation tone (or the corresponding evacuation tone delay
starts to count down)
Warning delay [1]
The optional delay before the sounders activate the warning tone
Delay [1]
The optional delay before the sounders activate the evacuation tone
[1] To configure these values, see “Sounder, fire routing, fire protection, and program output
group delays” on page 94.
Figure 24: Detector alarm with second stage delay
Figure 25: Detector alarm with standard delay (no second stage)
Warning tone
Evacuation tone
Warning time (or
second stage delay)
Warning delay
Delay
D
et
ec
tor
al
ar
m
R
es
et
Time
Evacuation tone
Delay
D
et
ec
tor
al
ar
m
R
es
et
Time
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......